Rolling Service Fire Doors


The FireKing® Models 630/631/634/635 rolling steel, fire-rated service doors offer superior protection wherever a listed fire door is required. Common applications include factories, warehouses, mills, distribution centers and parking garages. Customized fire doors are available for conveyor openings. These doors feature fusible links mounted on both sides of the wall that separate to automatically close the door. UL recommends a 165º F (74ºC) fuse link for ambient conditions for 100º F (38ºC) or less, or a 212º F (100ºC) fuse link for ambient conditions over 100º F (38ºC). Added protection features, such as Fire Sentinel® and FireLite® vision lites are optional.




Product Application Chart

Door
Label
Mounting Wall
Construction
Max.
Width
Max.
Height
Max.
Area
Certifying
Agency
4 Hr Label Face of Wall and Between the Jambs* Masonry/Steel 13'6" 13'-6" 152 Sq. Ft. UL
4 Hr Label Face of Wall and Between the Jambs* Masonry/Steel 12' 10' 120 Sq. Ft. FM
Oversize
4 Hr
Face of Wall and Between the Jambs* Masonry/Steel 41'2" 25'4" 683 Sq. Ft. UL
Oversize
4 Hr
Face of Wall and Between the Jambs* Masonry/Steel 18' 18' 324 Sq. Ft. FM
3 Hr Face of Wall and Between the Jambs* Non-Masonry 12' 12' 144 Sq. Ft. UL
1 1/2 Hr Face of Wall and Between the Jambs* Non-Masonry 12' 10' 117 Sq. Ft. FM
Oversize
3 Hr
Face of Wall and Between the Jambs* Non-Masonry 14' 12' 168 Sq. Ft. UL
Oversize
1 1/2 Hr
Face of Wall Non-Masonry 14' 11' 140 Sq. Ft. FM
Oversize
3 Hr
Face of Wall and Between the Jambs* Steel Tube Inside
Non-Masonry
16' 14' 224 Sq. Ft. UL
Oversize
1 1/2 Hr
Face of Wall Steel Tube Inside
Non-Masonry
14' 11' 140 Sq. Ft. FM
3 Hr Face of Wall Steel Tube Inside
Non-Masonry
12' 12' 144 Sq. Ft. UL
3 Hr Face of Wall Steel Tube on Masonry
or Non-Masonry
12' 10' 120 Sq. Ft. FM
Oversize
3 Hr
Face of Wall Steel Tube on Masonry
or Non-Masonry
24' 24' 576 Sq. Ft. UL
Oversize
3 Hr
Face of Wall Steel Tube on Masonry
or Non-Masonry
18' 18' 324 Sq. Ft. FM
* Between jambs doors are based on width of wall and from floor to top of coil (under lintel). Factory Mutual (FM) reviews each size above the over size service on a case-by-case basis






Standard Features at a Glance

Technical Data

Application - Exterior/Interior for fire rated walls
Operation - Non-motorized, mechanical floor resettable hoist with viscous governor
Mounting - Face of wall (between jambs optional)
Drop Speed - Meets NFPA 80 requirements of 6" to 24" per second

Models

  • 630 – Standard fire door
  • 631 – Smaller fire door
  • 634 – Fire door up to 24'x24'; 4 hour rating UL
  • 635 – Insulated fire door

Curtain

Material - Steel slats in a variety of gauges
Finish - Baked-on polyester top coat in Gray, Tan, White, or Brown
Guides - Three steel angles (some use structural and some are roll formed)
Bottom Bar - Steel double angle

Counterbalance System

Counterbalance - High tensile helical torsion spring housed in a steel tube or pipe
Brackets - Steel plates to support counterbalance, curtain, and hood

Limited Warranty

2-year material and workmanship 1-year labor




Available Options

Rolling Service Fire Doors
Fire Sentinal®

Time-delay release device
FireLite® Vision Lite
Available in 1-1/2 hr, 3 hr, and 4 hr labels
Rolling Service Fire Doors
Smoke Detectors
Heat Detectors
Photoelectric or ionization-type smoke detectors.
Heat detectors are also available.
Smoke Seal
UL-listed brush-type smoke seals (“S” label) to satisfy smoke retardation requirements of certain applications.
Flame Baffle System
A Factory Mutual (FM) requirement.
FM Label
FM labels are available in 1-1/2 hr, 3 hr, and oversized door.
Horns
Horns and horns with strobes are available.
Crank or Electric Operation
To satisfy a variety of applications. See page 10 for more detailed information.
  • Between jamb mount
  • Fire Sentinel® time-delay release device
  • FireLite® vision lite (Flat and insulated slats only with a max of 4 per door)
  • Smoke detectors and heat detectors
  • UL-listed brush-type smoke seals “S” label (flat or insulated slats only)
  • Flame baffle system - an FM requirement
  • UL, ULC and FM labels available
  • Horns and horns with strobes
  • Tension release: push-up or crank, electric motor: RHX® or RSX®
  • Non-tension hoist or electric motor: RSX® FDO* or RHX® FK • Stainless or galvanized steel: curtain, hood, guides, bottom bar
  • Slide bolts, cylinder locks, interlocks
  • Wind load options to include: Florida Building Code (FBC), Miami-Dade, Texas Department of Insurance (TDI)
  • PowderGuard® Premium powder coat in 197 standard colors or color-matched to specification
  • PowderGuard® Zinc and PowderGuard® Weathered finishes




Slat Data















Door Clearance Elevation


Operation: Push-up, crank, chain hoist, electric, RSX®, or RHX®.

Face of Wall Mounted

Between Jambs Mounted



Face-of-Wall Rolled Guides

Section B-B





Face of Wall Angle Guides

Section B-B





Between Jambs-Angle Guides

Drive Side - Electric, Chain, or Crank
Section B-B

Tension Side & Push-Up Drive Side
Section C-C




Downloadable Brochure and Warranty

Brochure Warranty
Syndicate content